新型夹芯保温叠合楼板的传热机理及热工性能研究
Research on the Heat Transfer Mechanism and Thermal Performance of Sandwich Thermal Insulation Composite Floor Slabs
2023年第5期
新型夹芯保温叠合楼板;热桥效应;桁架钢筋;参数化分析;传热系数;回归分析;数值分析
Sandwich thermal insulation composite floor slab; Thermal bridge effect; Truss bar; Parametric analysis; Thermal transmittance; Regression analysis; Numerical analysis
2023年第5期
10.19761/j.1000-4637.2023.05.068.06
贺庆澳1,2,张明山1,3,李本悦3,邓 华2,徐铨彪1,3
1.浙江大学平衡建筑研究中心,浙江 杭州 310058;2.浙江大学 建筑工程学院,浙江 杭州 310058;3.浙江大学建筑设计研究院有限公司,浙江 杭州 310063

贺庆澳1,2,张明山1,3,李本悦3,邓 华2,徐铨彪1,3

贺庆澳,张明山,李本悦,等.新型夹芯保温叠合楼板的传热机理及热工性能研究[J].混凝土与水泥制品,2023(5):68-73.

HE Q A,ZHANG M S,LI B Y,et al.Research on the Heat Transfer Mechanism and Thermal Performance of Sandwich Thermal Insulation Composite Floor Slabs[J].China Concrete and Cement Product,2023(5):68-73.

浏览量:
1000
摘  要:将保温层置于混凝土叠合楼板的预制底板和现浇顶板之间,提出了一种新型夹芯保温叠合楼板(以下简称新型叠合板),建立了稳态传热分析有限元模型,研究了桁架钢筋间距、夹芯层厚度等对新型叠合板传热系数的影响。结果表明:为满足规范传热要求,夹芯层厚度需超过20 mm、材料导热系数需小于0.15 W/(m·K);新型叠合板热桥效应明显,桁架钢筋对结构传热系数影响可达13.5%;随着夹芯层保温效果的提高,桁架钢筋间距造成的热阻变化占整体热阻的比例逐渐提高,但占钢筋总影响的比例降低。此外,通过对样本模型数据进行回归分析,得到了具有较高精度的传热系数计算公式,可以用来评估此类新型叠合板的保温性能。 Abstract: A new type of sandwich thermal insulation composite floor slabs was proposed, in which the thermal insulation layer was placed between the precast bottom plate and the cast-in-place top plate of reinforced concrete composite floor slabs. The effects of parameters, such as the spacing between the truss bars and the thickness of the sandwich layer, on the thermal transmittance of the sandwich thermal insulation composite floor slabs were investigated. The results show that, the thickness of sandwich layer should exceed 20 mm, and the thermal conductivity of the material should be less than 0.15 W/(m·K) to meet the heat transfer requirements of the specification. The thermal bridge effect of the sandwich thermal insulation composite floor slabs is obvious, with an impact on the thermal transmittance of the structure up to 13.5%. With the improvement of insulation effect of sandwich layer, the proportion of thermal resistance variation caused by the change of truss spacing to the overall thermal resistance gradually increases, but its proportion to the total influence of truss bars decreases. In addition, a new formula for calculating the thermal transmittance with high accuracy is obtained through the regression analysis of the sample model data, which can quickly evaluate the thermal insulation performance of this new type of composite floor slabs.
英文名 : Research on the Heat Transfer Mechanism and Thermal Performance of Sandwich Thermal Insulation Composite Floor Slabs
刊期 : 2023年第5期
关键词 : 新型夹芯保温叠合楼板;热桥效应;桁架钢筋;参数化分析;传热系数;回归分析;数值分析
Key words : Sandwich thermal insulation composite floor slab; Thermal bridge effect; Truss bar; Parametric analysis; Thermal transmittance; Regression analysis; Numerical analysis
刊期 : 2023年第5期
DOI : 10.19761/j.1000-4637.2023.05.068.06
文章编号 :
基金项目 :
作者 : 贺庆澳1,2,张明山1,3,李本悦3,邓 华2,徐铨彪1,3
单位 : 1.浙江大学平衡建筑研究中心,浙江 杭州 310058;2.浙江大学 建筑工程学院,浙江 杭州 310058;3.浙江大学建筑设计研究院有限公司,浙江 杭州 310063

贺庆澳1,2,张明山1,3,李本悦3,邓 华2,徐铨彪1,3

贺庆澳,张明山,李本悦,等.新型夹芯保温叠合楼板的传热机理及热工性能研究[J].混凝土与水泥制品,2023(5):68-73.

HE Q A,ZHANG M S,LI B Y,et al.Research on the Heat Transfer Mechanism and Thermal Performance of Sandwich Thermal Insulation Composite Floor Slabs[J].China Concrete and Cement Product,2023(5):68-73.

摘要
参数
结论
参考文献
引用本文

摘  要:将保温层置于混凝土叠合楼板的预制底板和现浇顶板之间,提出了一种新型夹芯保温叠合楼板(以下简称新型叠合板),建立了稳态传热分析有限元模型,研究了桁架钢筋间距、夹芯层厚度等对新型叠合板传热系数的影响。结果表明:为满足规范传热要求,夹芯层厚度需超过20 mm、材料导热系数需小于0.15 W/(m·K);新型叠合板热桥效应明显,桁架钢筋对结构传热系数影响可达13.5%;随着夹芯层保温效果的提高,桁架钢筋间距造成的热阻变化占整体热阻的比例逐渐提高,但占钢筋总影响的比例降低。此外,通过对样本模型数据进行回归分析,得到了具有较高精度的传热系数计算公式,可以用来评估此类新型叠合板的保温性能。

Abstract: A new type of sandwich thermal insulation composite floor slabs was proposed, in which the thermal insulation layer was placed between the precast bottom plate and the cast-in-place top plate of reinforced concrete composite floor slabs. The effects of parameters, such as the spacing between the truss bars and the thickness of the sandwich layer, on the thermal transmittance of the sandwich thermal insulation composite floor slabs were investigated. The results show that, the thickness of sandwich layer should exceed 20 mm, and the thermal conductivity of the material should be less than 0.15 W/(m·K) to meet the heat transfer requirements of the specification. The thermal bridge effect of the sandwich thermal insulation composite floor slabs is obvious, with an impact on the thermal transmittance of the structure up to 13.5%. With the improvement of insulation effect of sandwich layer, the proportion of thermal resistance variation caused by the change of truss spacing to the overall thermal resistance gradually increases, but its proportion to the total influence of truss bars decreases. In addition, a new formula for calculating the thermal transmittance with high accuracy is obtained through the regression analysis of the sample model data, which can quickly evaluate the thermal insulation performance of this new type of composite floor slabs.

扫二维码用手机看
未找到相应参数组,请于后台属性模板中添加

(1)若选用常规建筑流塑材料,夹芯层厚度需大于20 mm,材料导热系数需小于0.15 W/(m2·K)方可满足规范要求。在实际工程中,夹芯层推荐厚度为20~30 mm,推荐导热系数为0.07~0.15 W/(m2·K)。
(2)在新型叠合板中铺设桁架钢筋将形成较为显著的热桥效应,对整体结构热阻造成的影响比例可达到13.5%。
(3)随着新型叠合板保温效果的提高,热桥效应随之增强,桁架钢筋间距造成的热阻变化占总体热阻的比例逐渐提高,但占钢筋总体热阻比例降低。
(4)通过统计回归分析,对规范公式进行修正,给出了具有较高精度和适用性的新型叠合板传热系数计算公式。

[1] 中华人民共和国住房和城乡建设部.建筑节能与可再生能源利用通用规范:GB 55015—2021[S].北京:中国建筑工业出版社,2021.
[2] 李志铮.绿色建筑与声环境[D].北京:清华大学,2014.
[3] KOS L.Novel Thermal Insulation Materials for Buildings[J].Energies,2022,15(18):1-4.
[4] WANG J,DU B.Experiment on the Optimization of Sound Insulation Performance of Residential Floor Structure[J]. Applied Acoustics,2020,174(3):107734.
[5] TAWIL H,TAN C G,NOR S L,et al.Mechanical and Thermal Properties of Composite Precast Concrete Sandwich Panels:A Review[J].Buildings,2022,12(9):310-315.
[6]    OLIVER K,ROGER W,RICHARD O H.Structural Shear Performance of Insulated Precast Concrete Sandwich Panels with Steel Plate Connectors [J].Engineering Structures,2020,215(4):110691-110691.
[7] FRANK B A,LUCIER G W,HASSAN T K,et al.Behavior of Precast,Prestressed Concrete Sandwich Wall Panels Reinforced with CFRP Shear Grid[J].PCI Journal,2011(8):78-82.
[8] CHOI WC,JANG S J,YUN H D.Design Properties of Insulated Precast Concrete Sandwich Panels with Composite Shear Connectors [J].Composites:Part B,2018,157:852-863.
[9]    RICHARD O H,AIDAN R,ROGER W,et al.Thermal Investigation of Thin Precast Concrete Sandwich Panels[J]. Journal of Building Engineering,2020,27:100937.
[10]    DANIEL J,PRABAKAR J,ALAGUSUNDARAMORTHY P.Precast Concrete Sandwich One-Way Slabs Under Flexural Loading[J].Engineering Structures,2017,138:447-457.
[11] 谢剑,朱礼敏,戴自强.混凝土夹芯双向板的夹层板理论分析和有限元分析[J].土木工程学报,2005(7):39-44,121.
[12] 余泳涛,赵勇,高志强.单缝密拼钢筋混凝土叠合板受弯性能试验研究[J].建筑结构学报,2019,40(4):29-37.
[13] 中华人民共和国住房和城乡建设部.民用建筑热工设计规范:GB 50176—2016[S].北京:中国建筑工业出版社,2016.
[14] 杨柳.建筑物理(第5版)[M].北京:中国建筑工业出版社,2021.
[15] BOULBES R J.Troubleshooting Finite-Element Modeling with Abaqus:With Application in Structural Engineering Analysis[M].Switzerland:Springer,2020.

贺庆澳,张明山,李本悦,等.新型夹芯保温叠合楼板的传热机理及热工性能研究[J].混凝土与水泥制品,2023(5):68-73.

HE Q A,ZHANG M S,LI B Y,et al.Research on the Heat Transfer Mechanism and Thermal Performance of Sandwich Thermal Insulation Composite Floor Slabs[J].China Concrete and Cement Product,2023(5):68-73.

相关文件

暂时没有内容信息显示
请先在网站后台添加数据记录。

关注《混凝土与水泥制品》

总访问量 468,401   网站统计

官方微信公众号关闭
苏州混凝土水泥制品研究院有限公司

关于我们    |    联系我们    |    订购杂志    |    回到顶部

版权所有:中国混凝土与水泥制品网  苏ICP备10086386号   网站建设:中企动力 苏州

版权所有:中国混凝土与水泥制品网

苏ICP备10086386号

网站建设:中企动力 苏州